This driver allows JSup to connect with any device with the Modbus protocol over
TCP/IP.
Address
Telemecanique notation |
Modbus notation |
Description |
---|---|---|
%mw1000 |
401001 |
Word: in the Telemecanique notation is signed if the tag type is Short, Float or Double, otherwise it is unsigned; in the ModBus notation its unsigned (16 bits) |
%m1000 |
001001 |
Bit |
%iw1000 |
301001 |
Input word (16 bits) |
%i1000 |
101001 |
Input bit |
%mw1000S |
401001S |
Signed word (16 bits) |
%mw1000U |
401001 |
Unsigned word (16 bits) |
%md500 |
400501L |
Unsigned double word (32 bits) |
%mdl500 |
400501LD |
Unsigned 64 bit word |
%mf500 |
400501F |
Floating point (2 words, 32 bits) |
%mfl500 |
400501FD |
Double Floating point (4 words, 64 bits) |
%mw600,6 |
400601-400606M |
String of 12 characters stored on 6 consecutive words |
%mw700.3
|
400701,3
|
Single bit of a word |
%mw700.8-15 |
400701,8-F |
high byte of a word (unsigned) |
%mw700.0-1 |
400701,0-1 |
the 2 lower bits of a word (unsigned) |